Sizing an extraction system: airflow, ducts and pressure
Capture velocity, airflow, conveying velocity, pressure drop: the method for sizing an extraction installation, workstation by workstation.

01 / Sizing the extraction
1. The airflow of each hood
Start from the velocity to achieve at the emission point: 0.25 to 0.5 m/s for evaporation, 0.5 to 1 m/s for welding, 1 to 2.5 m/s for active emission, 2.5 to 10 m/s for grinding (INRS ED 695). The shape of the hood and its distance give the airflow: for a plain opening, Q = V × (10 X² + A).
The total airflow is the sum of the hoods used at the same time. The volume of the room does not enter this calculation: it is used for general ventilation, not for capture.
02 / Sizing the extraction
2. Duct diameters
Each section is sized to maintain the conveying velocity of the pollutant: more than 7 m/s for fumes, 18 to 20 m/s for grinding dust, more than 20 m/s for heavy dust. Cross-section = airflow ÷ velocity.
Our online tool calculates the diameter and pressure drop of a duct section.
03 / Sizing the extraction
3. Pressure drop
Add up, branch by branch, the losses of straight sections, bends and junctions, the hood and the clogged filter. The most unfavourable branch sets the pressure; the others are balanced with dampers.
The fan is selected at this operating point: total airflow and pressure of the most unfavourable branch.
04 / Sizing the extraction
A complete example: three grinding stations
Three bench grinders, each captured by a Ø 150 opening 10 cm from the wheel at 2.5 m/s: 1,060 m³/h per station. Two stations work at the same time: the airflow to handle is 2,120 m³/h.
Branches: Ø 140 mm, i.e. 19 m/s. Common main duct: Ø 180 mm, i.e. 23 m/s. The velocity stays above the 18 to 20 m/s needed to convey grinding dust.
The pressure drop of the longest branch, including hood and clogged filter, gives the fan pressure. For continuous grinding, a DAS CC with on-line cleaning.
05 / Sizing the extraction
4. The file to send us
A layout with the position of the workstations, the list of operations and materials, the workstations running simultaneously, photos of the workstations and the planned location of the filter. For existing ductwork, the diameters, lengths and bends, and the fan references.
Useful answers
Frequently asked questions
Can extraction be sized from the volume of the building?
No. The volume is used to calculate general ventilation. Capture is sized workstation by workstation, from the hoods.
Why give the pressure as well as the airflow?
Because a fan only delivers its airflow at a given pressure. Without the pressure drop of the ductwork and the filter, the stated airflow is not the one obtained at the workstations.
How is the extraction airflow of a dust collector calculated?
Calculate the airflow of each hood, then add up those that operate at the same time. The dust collector is selected at this airflow, at the ductwork pressure.
Continue your selection
Related solutions and guides
Your industrial project
Tell us what you need.
Send us photos of the workstations, the materials worked, which workstations run at the same time and your working hours: we size the capture and filtration and send you a costed quote.
Contact us
Let’s talk about your installation.
A technician from our engineering office studies your needs and proposes the right solution for your workshop: machine, capture, ductwork and filtration.
Reply within 48 working hours.
Your request, step by step
-
1
You describe your needs
Pollutant, workstations, constraints: a few lines are enough. A photo of the installation helps us a lot.
-
2
Our engineering office studies it
Capture, airflow, ductwork and filtration are sized for your site, together with you if anything needs clarifying.
-
3
You receive a written proposal
Machine, options and price, in detail: you decide with full knowledge of the facts.
- Since 1994in industrial air treatment
- In-house engineering officefrom design to supply
- All brandsfilters and spare parts
- French Fabnetwork member